Systems With Low Pressures On Both Sides back  

  Symptom
  System reflects low pressures on both sides and is not cooling adequately. The Evaporator is warm to the touch, and there are visable bubbles/foam in the sight glass.
Cause
System is suffering from an inadequate charge of refrigerant.
Solution
Check system for leaks and repair. Recharge the system Remember the loss of freon also results in a loss of oil. Make sure to add oil as well as refrigerant!

  Symptom
  System reflects low pressures on both sides and is not cooling adequately. However the drier is cool or cold to the touch.
Cause
This system is showing signs of a restriction in the drier itself.
Solution
Replace the drier and flush the system as the desiccant bag has probably ruptured and contaminated the system.

  Symptom
  System reflects low pressures on both sides and is not cooling adequately. However the drier is warm or hot to the touch.
Cause
This system is showing signs of a plugged or defective expansion valve.
Solution
Replace the expansion valve and flush the system as this is probably a result of debris in the system.